TYPICAL WIRING
AND CONFIGURATION 1F95-0680
CONFIGURATION MENU
Menu
Ref. HP SS
Press
Button
Displayed
Factory (Default)
Press or to
select from listed options COMMENTS
18 17 – MENU (On) Heat FA OFF Fast Heat option may be disabled by
selecting OFF. NA to SS or HP1 config.
19 18 – MENU (On) Cool FA OFF Fast Cool option may be disabled by
selecting OFF. NA to SS or HP1 config.
20 19 17 MENU Remote (OFF) On Selects Remote Sensor On/OFF
MENU Remote
(In)
Outdoor Selects Remote Sensor to outdoor
NA is Remote Sensor OFF
MENU Indoor Loc
(On)
OFF Selects Local Sensor (in thermostat) to OFF.
N/A if Remote is selected to Outdoor
21 20 18 MENU (On) dS Off Selects Automatic Daylight Saving Time option
22 21 19 MENU (OFF)
Keypad Lockout
L, P, Limit Selects one of 3 Keypad Lockout configurations
L - Total Keypad Lockout
P - Partial Keypad Lockout
(Up and Keys still work)
Limit - Limited Temperature Range
MENU (000)
Keypad Lockout
1-999 Selects personal lockout code. 000 is NOT A VALID CODE.
23 22 20 MENU (99) L Heat L 62 to L 98 Select's Limited HEAT Range
24 23 21 MENU (45) L Cool L 46 to L 82 Select's Limited COOL Range
25 24 – MENU (05) CO 6-50 Selects outdoor Compressor OFF temperature (Balance Point
temperature). 05 disables feature. Outdoor Remote required
MENU (dF) EA
Selects between dF (dual Fuel) or EA (Electric Aux)
only available if CO > 6
MENU (60) Cd Selects Compressor delay OFF time in seconds
26 25 – MENU (80) AO Selects AO (Auxiliary OFF) temperature. Feature disabled
if 80 is selected. Outdoor Remote required
27 26 22 MENU (OFF) EC On Selects Economizer On/OFF.
28 27 23 MENU (O) pp 1-3 Selects no. of hours of preoccupancy purge time (hours the
Fan runs (C an A1 energized) prior to occupied period)
29 28 24 MENU (OFF) Change Filter On Selects Filter Change-out Indicator On or OFF.
MENU Change Filter (200 h) 25-1975 h Change Filter time in 25 hour increments. This menu only
appears if On is selected in above.
30 29 25 MENU (OFF)
Change UV Lamp
On Selects UV Lamp Timer: On/OFF
MENU (350)
Change UV Lamp
25-1975 Selects no. of Days between changing UV Lamp
31 30 26 MENU (o) Cool On Heat On (b) Selects operation of the reversing valve terminal
(O/B) output as an O or B terminal
32 31 27 MENU Return to Normal Operation
INSTALLER/CONFIGURATION MENU (cont.)
TECHNICAL HELP
www.white-rodgers.com
143