FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE
INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL
INJURY AND/OR PROPERTY DAMAGE.
Type 1131 controls are designed for use on hot water
heating installations. They have single-pole, double-throw
switch action, offering open-on-rise terminals as well as
close-on-rise terminals. These controls may be used as a
high limit, low limit, circulator, or combination low limit-
circulator control.
Models are available with either horizontal or vertical well,
and with either fixed or adjustable differential. Some of
these models also have excess capillary stored within the
enclosure, permitting them to be used with wells having
either a standard or extended shank.
Another model, ideal for replacement purposes, has both
a slotted case and excess capillary stored within the
enclosure. This control can be used with either a standard
or extended shank well, on either horizontal or vertical
well installations.
DESCRIPTION
TYPE 1131
HOT WATER CONTROL
S.P.D.T. Well-Immersion
INSTALLATION INSTRUCTIONS
CAUTION
WARNING
THIS CONTROL MUST BE INSTALLED BY A
QUALIFIED INSTALLER.
Do not exceed the specification ratings.
All wiring must conform to local and national electrical
codes and ordinances.
This control is a precision instrument, and should be
handled carefully. Rough handling or distorting compo-
nents could cause the control to malfunction.
This control has been accurately calibrated at the factory.
Any attempt to calibrate this control will void the White-
Rodgers warranty.
PRECAUTIONS
CONVERTIBLE CONTROLS
Convertible controls have a Knockout Plate on back of
case (secured by Hex Nut on Horizontal models, and by
Knockout Plug on Vertical models). To convert from
Horizontal to Vertical:
1. Remove control cover. Then remove bottom knockout.
2. Remove Hex Nut (inside control) from Well Mounting
Stem. (To loosen, hold Hex Nut inside while turning
Hex Nut on back of control counterclockwise.)
3. Pull Well Mounting Stem away from case and remove
Knockout Plate.
4. Swing capillary down through slot into bottom knock-
out.
5. Secure Knockout Plate to back of case by using
Knockout Plug provided in envelope.
6. Insert Well Mounting Stem into bottom knockout and
tighten Hex Nut (inside control) securely.
WHITE-RODGERS
Operator: Save these instructions for future use!
PART NO. 37-2071B
Replaces 37-2071 & 37-9195
9548
Do not use on circuits exceeding specified
voltages. Higher voltages will damage control
and could cause shock or fire hazard.
To prevent electrical shock and/or equipment
damage, disconnect electric power to system, at
main fuse or circuit breaker box, until installation
is complete.
Vista de página 0
1 2 3 4 5 6

Resumo do Conteúdo

Página 1 - WHITE-RODGERS

WHITE-RODGERS DIVISIONEMERSON ELECTRIC CO.9797 REAVIS RD., ST. LOUIS, MO. 63123(314) 577-1300, FAX (314) 577-15179999 HWY. 48, MARKHAM, ONT. L3P 3J3

Página 2 - EXTENDING CAPILLARY

2CONVERTIBLE CONTROLS CONT.To convert from Vertical to Horizontal model, removeKnockout Plug and Plate. Remove Hex Nut (inside con-trol) and swing cap

Página 3 - WIRING (CONT.)

3Diagram For Gas Or Oil Fired System With Tankless Domestic CoilXX24 VACGAS VALVEHIGH LIMITTRANS.The R-B contacts of the low limit-circulator control

Página 4

ATTENTIONAfin de prévenir les chocs électriques et lesdommages matériels pendant l’installation,coupez l’alimentation électrique au panneau dedistribu

Página 5 - EXTENSION DU CAPILLAIRE

2NOTEPour convertir la commande de la verticale à l’horizontale,retirer d’abord le bouchon et la plaque de conversion.Retirer l’écrou hexagonal (à l’i

Página 6 - RÉGLAGE DE LA COMMANDE

3W1423BRJUMPERWBRX XXXcontinuera de fonctionner, mais le brûleur s’arrêtera jusqu’àce que le limiteur à maximum soit à nouveau fermé.Lorsque la tempér