If you want to change the preprogrammed times
and temperatures, follow these steps.
1. Determine the heating and cooling tem-
peratures you want to use. You may select
up to two heating temperatures (HEAT A
and HEAT B), and up to two cooling tem-
peratures (COOL A and COOL B). Use the
table on the next page to write down the
temperatures you have selected. Keep in
mind that you can program up to 4 tempera-
tures (2 heating, 2 cooling) at a time.
To operate properly in the AUTO mode, there
must be a minimum 1°F separation between
the highest heat temperature and the lowest
cool temperature (see diagram below).
NOTE
79
78
77
76
75
74
73
COOLING TEMPERATURES
HEATING TEMPERATURES
DEAD BAND 1°F
Heating Program for ALL days of the Week:
Cooling Program for ALL Days of the Week:
PERIOD TIME TEMP PERIOD TIME
TEMP
1
2
3
4
5:00 AM
8:00 AM
5:00 PM
10:00 PM
64
70
64
64
1
2
3
4
5:00 AM
8:00 AM
5:00 PM
10:00 PM
82
78
82
82
FACTORY PREPROGRAMMING